Specifications
pH Range 4.0 – 10.0
pH Display Resolution 0.1
ORP Range 0 – 1000 mV
ORP Display Resolution – 1mV
CI/ppm Range 0.1 – 12.0+ ppm
CI/ppm Display Resolution 0.1 ppm
Input Power – 120 VAC 60 Hz, 1/8 Amp, excluding pumps, 3 wire grounded plug GFCI source required.
Output Power – (2) switched 3-wire grounded outlets, 120 VAC 60 Hz, 6 Amps cumulative, fused
Display – 2 x 16 character back-lit LCD digital display, multi-color flashing LED indicator
Enclosure – ABS NEMA 12 with hinged cover and latching device
Size – 9.0” x 7.3” x 3.4”
Weight 3.0lbs
Selectable Parameters included:
- Proportional, set-point, or manual chemical feed
- Ideal pH, ORP, and CI/pp, settings
- Upper and lower alarm limits to establish acceptable operating range for pH, ORP and CI/ppm
- CI/ppm display dependent on pH (or assume pH is 7.5)
- pH dosing either acid or base
- Sanitizer control either CI/ppm or ORP
- Standard 1-minute cycle and 0.5 ppm span for CI/ppm control (20mV span for ORP control)
- Programmable cycle and span for proportional feed
- Lag compensation with DPMC control
- Safety lockouts for excessive or insufficient feed
- Visual alarms for out-of-range or non-correctable conditions
Options and Accessories
- pH and ORP Probes
- Chemical pumps and actuators
- Flow switch ready pre-write
- Piston and rotary flow switches
- DPMC control software
- Bypass lines
- Probe sample chambers
- Installation pluming kits